When installing the power line on the UPS5000-E, if there are different sources on the main-lines and bypass, you need to remove the copper bars connected to the bypass and main lines first, and then connect the main circuit and bypass input respectively.
NeteCol can assign operational rights to user groups, or assign operational rights directly to users.
Before the battery is installed, a single battery open circuit voltage is required: 12V battery is greater than or equal to 12.60V or 2V battery is greater than or equal to 2.10V. When it is found to be unqualified, the battery needs to be recharged.